Surge Protection Device (SPD): Types, Classes and Where to Use Them

A surge protection device (SPD) is a component fitted into an electrical installation to divert transient overvoltages to earth before they reach equipment. There are three types — Type 1, Type 2 and Type 3 — and they are not alternatives to one another. Each is tested against a different impulse waveform, each sits at a different point in the installation, and a complete installation normally uses all three in a coordinated chain.

If you have seen SPDs described as Class B, C and D, that is the older German/VDE naming for the same three positions. The mapping is below.

What a surge protection device actually does

Under normal voltage an SPD is effectively an open circuit and does nothing. When the voltage rises past its threshold it switches to a low-impedance state in nanoseconds, shunting the surge energy to the earthing system and clamping the voltage that appears across the load. Once the transient has passed it returns to its blocking state.

That description carries an important consequence: an SPD is only as good as the earth it discharges into. Fitted to a high-resistance or poorly bonded earth, it has nowhere to send the energy and the protection level you paid for is not achieved. This is why surge protection and earthing are one project, not two.

The three types of surge protection device

Type 1Type 2Type 3
Older class nameClass BClass CClass D
Tested withIimp, 10/350 µs impulse currentIn / Imax, 8/20 µs impulse currentCombination wave (1.2/50 µs voltage, 8/20 µs current)
SimulatesPartial direct lightning currentInduced and switching surgesResidual transients close to the load
Installed atOrigin of the installation — main LT panel / service entranceSub-distribution boardsSocket outlet or equipment level
Required whenThe structure has an external lightning protection system, or is fed by an overhead line, or shares an earth with a struck structurePractically every installationSensitive electronics: PLCs, BMS, servers, medical, instrumentation
Used alone?No — needs Type 2 downstreamYes, in low-exposure installationsNo — must sit behind a Type 2

Type 1 (Class B)

Type 1 devices are the only ones rated to handle partial lightning current — the 10/350 µs waveform, which carries far more energy than the 8/20 µs wave used to test Type 2. They belong at the service entrance of any building that has an external lightning protection system, is fed from an overhead line, or is bonded to an earth that a strike can reach. A Type 2 device installed in that position will be destroyed by the first real event.

Type 2 (Class C)

The workhorse. Type 2 SPDs at distribution boards handle induced surges from nearby strikes, switching transients from motors and capacitor banks, and whatever energy passes a Type 1 upstream. Key ratings to read on the label are In (nominal discharge current, the level it can take repeatedly), Imax (maximum single discharge) and Up (the voltage protection level — what actually reaches your equipment).

Type 3 (Class D)

Low-energy devices fitted at or near the load to bring the residual voltage down for genuinely sensitive electronics. A Type 3 device on its own in front of an otherwise unprotected installation is not protection — it has nothing like the energy capacity for an upstream event, and it will fail.

Class B / C / D vs Type 1 / 2 / 3

They describe the same three duties. Class B = Type 1, Class C = Type 2, Class D = Type 3. The Type numbering comes from IEC/EN 61643-11, which defines the test classes; the Class B/C/D naming is the older German convention that is still widely used in specifications and catalogues across India. If a drawing calls for a “Class C SPD at the sub-board”, supply a Type 2 — but check the stated Up, In and Uc rather than assuming equivalence between two catalogue items with the same letter.

How to coordinate them

  • Put the stages in order. Type 1 at the origin, Type 2 at sub-distribution, Type 3 at the load. Energy is stepped down at each stage.
  • Give the stages separation. Coordination relies on cable impedance between devices — roughly 10 m of cable between stages is the usual rule of thumb. Where that distance does not exist, use a decoupling inductor or a manufacturer-coordinated combined device.
  • Keep the connecting leads short. This is the most common installation error. The voltage that reaches your equipment is the SPD’s Up plus the inductive drop along its connecting leads. Aim to keep the total lead length of the SPD connection within about 0.5 m; a neatly dressed 1.5 m loop can double the let-through voltage.
  • Fit the specified backup protection. SPDs need an overcurrent device — a fuse or MCB of the rating the manufacturer states — so that an end-of-life SPD disconnects safely instead of failing short.
  • Check Uc against the supply. The maximum continuous operating voltage must sit above the highest steady-state voltage your system can present, or the SPD will age fast in an installation with a weak or unbalanced supply.
  • Earth it properly. Short, low-impedance path to a verified earth. See acceptable earth resistance values as per IS 3043.

Specialised SPDs

  • Solar / PV DC SPDs — rated for DC string voltages and fitted on both the array and inverter sides. See lightning protection for solar panels.
  • Street lighting SPDs — compact devices inside the pole or luminaire, where a long overhead or shallow-buried run makes induced surges routine.
  • Data and signal SPDs — for Ethernet, RS-485, instrumentation loops and telecom lines. Protecting only the power side and leaving the signal side open is a very common way to lose a PLC.
  • Combined Type 1+2 devices — a single unit for small installations where there is no room for a coordinated pair.

How to choose — a short checklist

  1. Does the building have an external LPS or an overhead supply? If yes, you need Type 1 at the origin.
  2. What is the system earthing arrangement (TN-S, TN-C-S, TT) and the nominal voltage? This sets Uc and the connection mode.
  3. What is the lowest withstand voltage among the equipment you are protecting? Choose a device whose Up sits comfortably below it.
  4. How exposed is the site — lightning density, overhead lines, switching loads nearby? This sets In and Imax.
  5. Is there sensitive electronic equipment? Add Type 3 locally, and do not forget the signal lines.
  6. Is there a status indicator or remote contact so a failed SPD is noticed? An SPD that has done its job once and is now dead looks identical from outside.

Selecting SPDs for a project

Ashlok supplies surge protection devices alongside the lightning protection and earthing they depend on, so the three are specified together rather than bolted on afterwards. Send us your single-line diagram and the site exposure and we will mark up the SPD positions and ratings. Call +91 94440 87356 or contact us.

Frequently asked questions

What is the full form of SPD?

Surge Protection Device. It is also called a surge protective device, a surge arrester or a transient voltage surge suppressor (TVSS) in older documentation.

What is the difference between a Class B and a Class C SPD?

Class B (Type 1) is tested with the high-energy 10/350 µs waveform and is designed to carry partial lightning current at the service entrance. Class C (Type 2) is tested with the 8/20 µs waveform and handles induced and switching surges at distribution boards. Class C cannot substitute for Class B where direct lightning current is possible.

Do I need all three types?

Not always. A building with no external lightning protection, an underground supply and no sensitive electronics may be adequately served by Type 2 alone. A building with an LPS and a control room needs all three, coordinated.

Which standard covers SPDs?

IEC/EN 61643-11 covers low-voltage power system SPDs and defines the Type 1/2/3 test classes. Selection and installation within a lightning protection scheme is addressed by IEC 62305-4.

Where exactly should a Type 2 SPD be installed?

In the distribution board it protects, as close to the incoming terminals as the enclosure allows, with the shortest possible connecting leads to the live conductors and to the earth bar.

How long does an SPD last?

There is no fixed life — it depends on how many surges it absorbs. SPDs degrade with each event, which is why status indicators and remote signalling contacts exist. Include SPD status in the routine electrical inspection.