Short answer: a lightning arrester earth pit is normally designed to a target of 10 Ω or less, measured at low frequency, and bonded to the building’s main earthing system. That 10 Ω figure is a practical design target used across IEC 62305-3 practice and for early streamer emission (ESE) air terminals under NFC 17-102 — not a magic pass mark. Lower is better, and what matters just as much is how the earth termination is laid out and whether it can be tested for the life of the building.
This guide explains what value to aim for, how a lightning earth differs from an ordinary power earth, how many pits a system needs, and what to do when the reading comes back high. For general power-earthing limits, see our guide to acceptable earth resistance values as per IS 3043.
What is the acceptable earth resistance for a lightning arrester?
| Context | Commonly used target | Where it comes from |
|---|---|---|
| Lightning protection earth termination (conventional air terminals) | 10 Ω or lower, measured at low frequency | Recommendation in IEC 62305-3; widely written into Indian project specifications |
| ESE lightning arrester (early streamer emission) | 10 Ω or lower per earth pit | NFC 17-102 installation requirements |
| Power system / equipment earthing | Per the project design and IS 3043 — often lower for sensitive loads | IS 3043 and the electrical designer’s fault study |
| Combined system (lightning earth bonded to main earth) | Whole-system value is what counts | Bonding all earths together is the accepted approach; see below |
Two cautions. First, a specification written for your project always overrides a rule of thumb — if the consultant says 5 Ω, design to 5 Ω. Second, a low number alone does not make a good lightning earth. A lightning current is fast and large, so IEC 62305-3 also cares about the shape of the earth termination: ring conductors or several well-spread electrodes behave far better than one deep rod at the same resistance.
How a lightning earth differs from a power earth
- Frequency of the current. A fault current is mains frequency. A lightning impulse rises in microseconds, so the impedance of the earth path — including the length and bends of the conductor — matters as much as the DC resistance of the pit.
- Layout over depth. IEC 62305-3 describes Type A (individual electrodes at each down conductor) and Type B (a ring conductor or foundation earth). Spreading the electrodes lowers the potential rise around the building.
- Bonding. Lightning earthing is bonded to the main earth bar so there is no dangerous potential difference between systems. Separate, isolated lightning earths are not recommended.
- Separation from people. Pits are kept clear of walkways and doorways where step voltage could be a risk.
How many earth pits does a lightning arrester need?
The number is set by the design, not by habit. As a working guide for a conventional system, each down conductor ends in its own earth electrode, and the electrodes are interconnected by a buried ring or by the main earth grid. For an ESE air terminal there is usually a minimum of two down conductors and an earth pit for each, depending on the manufacturer’s installation instructions and the protection level chosen. If the reading is above target, add electrodes in parallel and keep them spaced — a rule of thumb is at least the electrode length apart — so they do not share the same soil volume.
Specify earth pits that can be tested: Ashlok earthing electrodes with a test link in an earth pit chamber.
How to measure the value
- Open the test link so the electrode under test is isolated from the rest of the system.
- Use a fall-of-potential earth tester with the current and potential probes in a straight line, well clear of the pit.
- Take readings at several probe positions and confirm they settle on a plateau — the method is explained step by step in how to check earthing resistance.
- Test in the driest part of the year if you can; a reading taken just after rain flatters the pit. Record the date, soil condition and instrument.
- Re-bolt the link and re-measure the bonded system value.
What to do if the reading is too high
- Add parallel electrodes at proper spacing — the usual and most reliable fix.
- Improve the soil contact with a low-resistivity backfill around the electrode; see backfill compounds for different soils.
- Check the joints. A corroded clamp can add more resistance than the soil. Welded joints remove the problem — see our exothermic welding kit.
- Calculate before you drive. Soil resistivity decides how many electrodes you need; the working is in earth electrode resistance calculation.
Frequently asked questions
Is 10 ohm acceptable for a lightning arrester earth pit? Yes, 10 Ω or lower is the common design target for lightning protection earths, unless your project specification demands a tighter value.
Can I use the same earth pit for the lightning arrester and the electrical panel? Lightning earthing is bonded to the main earthing system, but the lightning down conductors should still terminate in their own electrodes, interconnected with the main earth through the bonding conductor or ring.
Does a lower earth resistance mean better lightning protection? Lower is helpful, but layout, bonding and joint quality matter just as much. A well-laid ring at 8 Ω can outperform a single deep rod at 5 Ω.
How often should the lightning earth be tested? At commissioning, then periodically — commonly once a year and before the monsoon — and after any strike or major civil work near the pits.
Which standards apply? IS/IEC 62305-3 and IS 3043 for the earth termination, and NFC 17-102 for ESE air terminals. Always follow the standard your project specification names.
Ashlok has manufactured earthing and lightning protection products since 1999. Explore lightning protection systems → · Related: ESE lightning arrester guide and lightning arrester for home.