Earthing accessories are the parts between the electrode and your equipment: the earth busbar, earth strip, test link, connectors and clamps, and the pit chamber cover. An electrode only does its job if these parts carry fault current reliably and stay accessible for testing. This guide lists each accessory, what it does, which material to choose, and how they fit together.
Types of earthing accessories and what each one does
| Accessory | What it does | Common materials | Choose it by |
|---|---|---|---|
| Earth busbar | Common bonding point where all earth conductors meet | Copper bar on insulated or galvanised-steel supports | Cross-section against fault current; Ashlok busbars come in sections such as 25×3, 40×6 and 50×6 mm |
| Earth strip | Routes the earth connection along walls, trenches and structures | GI (economy) or copper (lowest resistance, corrosive sites) | Fault current and duration, plus soil and atmosphere |
| Test link | Isolates one electrode for resistance measurement | Gunmetal, brass, GI or copper | Same size as the earthing conductor; see earthing test link guide |
| Connectors and clamps | Join rod to cable, cable to strip, strip to strip | Brass, bronze or copper alloy; or welded | Compatible metals, proper tightening, accessible for inspection |
| Exothermic weld joint | Permanent fused connection with no bolts to loosen | Copper-based weld metal in a graphite mould | Conductor and rod sizes; see the exothermic welding kit |
| Earth pit chamber cover | Protects the pit and keeps the test link reachable | HDPE, FRP, polymer concrete, RCC, cast iron | Load rating and location; see the chamber cover guide |
See the full range → Ashlok Earthing Accessories
Copper or GI earth strip — which should you use?
Copper gives the lowest resistance and the longest life in corrosive or coastal conditions, and it is the natural partner for copper-bonded electrodes. Hot-dip galvanised steel strip is the economical choice for general buried and surface routing, provided the zinc coating is intact and the joints are protected. The deciding factors are the fault current the strip must carry, the soil and atmosphere, and the budget. Avoid mixing bare metals at joints in damp locations — dissimilar-metal contact is a classic source of slow corrosion.
Bolted clamp or welded joint?
A mechanical clamp is quick and can be opened for testing, but in damp soil it can loosen and corrode, and its resistance can creep up unnoticed. A welded joint fuses the conductors into one piece of metal, so there is nothing to loosen. The usual practice is to weld permanent underground joints and keep one deliberate, accessible bolted point — the test link — for measurement. The reasoning is explained in our exothermic welding guide.
How the accessories fit together in a typical earth pit
- The electrode (for example a chemical or copper-bonded electrode) is installed in the pit.
- A welded or clamped joint connects the electrode to the earth conductor.
- The test link sits in the conductor inside the chamber.
- The chamber cover on top keeps it clean and findable.
- The conductor runs as earth strip or cable to the earth busbar, where all equipment earths are bonded.
Checklist: choosing earthing accessories
- Size to the fault current — strip and busbar cross-section must carry the prospective fault current for the clearing time without overheating. Take the figure from your electrical designer.
- Match the materials — copper with copper; keep dissimilar metals out of damp joints.
- Always include a test link so resistance can be measured over the system’s life.
- Prefer welded joints for permanent underground connections.
- Buy a compatible set — connectors, strips and busbars from one manufacturer fit and perform together.
Why accessories matter for compliance
IS 3043 expects an earthing system that can be inspected and tested. The right accessories — above all the test link and an accessible chamber — are what make that possible. Without them a system may work on day one but cannot be verified or maintained. For the target values to test against, see earth resistance values as per IS 3043.
Frequently asked questions
What are earthing accessories? The parts that connect and protect an earth electrode: busbar, strip, test link, connectors, welded joints and the chamber cover.
What is an earth busbar for? It is the common bonding point where all earth conductors meet, giving one clean earth reference for the installation.
Copper or GI strip? Copper for the lowest resistance and corrosive or coastal sites; GI where cost is the priority and joints will be protected.
Do accessories need to match the electrode? Yes — size them to the same fault current and use compatible metals and connectors.
Are welded joints better than clamps? For permanent underground connections, yes; keep the test link as the one openable joint.
Ashlok manufactures earthing accessories alongside its electrodes and lightning protection, since 1999. Explore earthing accessories → · New here? Start with what is earthing.